ABB Relion 650 Series Technical Manual page 366

Bay control
Hide thumbs Also See for Relion 650 Series:
Table of Contents

Advertisement

Section 10
Monitoring
Name
Mode
PowAmpFact
PowAngComp
k
Table 288:
CVMMXN Non group settings (advanced)
Name
SDbRepInt
SZeroDb
SHiHiLim
SHiLim
SLimHyst
PDbRepInt
PZeroDb
PHiHiLim
PHiLim
PLowLim
PLowLowLim
PLimHyst
QDbRepInt
QZeroDb
QHiHiLim
QHiLim
QLowLim
QLowLowLim
QLimHyst
Table continues on next page
360
Values (Range)
Unit
L1, L2, L3
-
Arone
Pos Seq
L1L2
L2L3
L3L1
L1
L2
L3
0.000 - 6.000
-
-180.0 - 180.0
Deg
0.000 - 1.000
-
Values (Range)
Unit
1 - 100000
Type
0 - 100000
m%
0.0 - 2000.0
%SB
0.0 - 2000.0
%SB
0.000 - 100.000
%
1 - 100000
Type
0 - 100000
m%
-2000.0 - 2000.0
%SB
-2000.0 - 2000.0
%SB
-2000.0 - 2000.0
%SB
-2000.0 - 2000.0
%SB
0.000 - 100.000
%
1 - 100000
Type
0 - 100000
m%
-2000.0 - 2000.0
%SB
-2000.0 - 2000.0
%SB
-2000.0 - 2000.0
%SB
-2000.0 - 2000.0
%SB
0.000 - 100.000
%
Step
Default
-
L1, L2, L3
0.001
1.000
0.1
0.0
0.001
0.000
Step
Default
1
10
500
1000
0.1
150.0
0.1
120.0
0.001
5.000
1
10
500
1000
0.1
150.0
0.1
120.0
0.1
-120.0
0.1
-150.0
0.001
5.000
1
10
500
1000
0.1
150.0
0.1
120.0
0.1
-120.0
0.1
-150.0
0.001
5.000
1MRK 511 424-UEN B
Description
Selection of measured current and
voltage
Amplitude factor to scale power
calculations
Angle compensation for phase shift
between measured I & U
Low pass filter coefficient for power
measurement, U and I
Description
Cycl: Report interval (s), Db: In 0,001%
of range, Int Db: In 0,001%s
Magnitude zero point clamping in
0,001% of range
High High limit in % of SBase
High limit in % of SBase
Hysteresis value in % of range, common
for all limits
Cycl: Report interval (s), Db: In 0,001%
of range, Int Db: In 0,001%s
Magnitude zero point clamping in
0,001% of range
High High limit in % of SBase
High limit in % of SBase
Low limit in % of SBase
Low Low limit in % of SBase
Hysteresis value in % of range, common
for all limits
Cycl: Report interval (s), Db: In 0,001%
of range, Int Db: In 0,001%s
Magnitude zero point clamping in
0,001% of range
High High limit in % of SBase
High limit in % of SBase
Low limit in % of SBase
Low Low limit in % of SBase
Hysteresis value in % of range, common
for all limits
Bay control REC650 2.2 IEC
Technical manual

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rec650