General start matrix block SMAGAPC

Identification
Function Description
Generat start matrix block
Functionality
The Start Matrix (SMAGAPC) merges start and directional output signals from
different application functions and creates a common start and directional output
signal (STDIR) to be connected to the Trip function, see Figure 129.
The purpose of this functionality is to provide general start and directional
information for the IEC 61850 trip logic data model SMPPTRC.
Function block
SMAGAPC
BLOCK
STDIR
STDIR1
STDIR2
STDIR3
STDIR4
STDIR5
STDIR6
STDIR7
STDIR8
STDIR9
STDIR10
STDIR11
STDIR12
STDIR13
STDIR14
STDIR15
STDIR16
IEC16000165-1-en.vsdx
IEC16000165 V1 EN-US
Figure 129:
SMAGAPC function block
Signals
Table 148:
SMAGAPC Input signals
Name
Type
BLOCK
BOOLEAN
STDIR1
INTEGER
STDIR2
INTEGER
STDIR3
INTEGER
Table continues on next page
IEC 61850
IEC 60617
identification
identification
SMAGAPC
-
Default
Description
0
Block of function
0
Start direction input 1
0
Start direction input 2
0
Start direction input 3
Section 9
Logic
GUID-C6D3DE50-03D2-4F27-82FF-623E81D019F4 v1
ANSI/IEEE C37.2
device number
-
GUID-BA516165-96DE-4CD9-979B-29457C7653C0 v3
GUID-99B1DF71-F7C4-4954-8688-BC709C3C2A16 v1
PID-6906-INPUTSIGNALS v2
281