Identification - ABB Relion 650 Series Technical Manual

Bay control
Hide thumbs Also See for Relion 650 Series:
Table of Contents

Advertisement

Section 13
Station communication
13.7.14.2
13.7.14.3
13.7.14.4
574
Input POSITION is a double-indication signal, and it is GI enabled. This means
that any state transition, that is to ON, OFF, intermediate and faulty, is reported
spontaneously. However, the intermediate and faulty states may be suppressed by
setting the Report Intermediate Position = Off. See the settings for RS485 and
optical serial communication for more information.
Input SELECT is a single-indication signal, and it is also GI enabled. State
transitions to ON and OFF are reported spontaneously.
When input BLOCK is ON, the function will ignore GI requests and cease all
monitoring activity. Consequently, no transitions will be detected.
The I103POSCMD function is also equipped with three additional commands:
Select, Operate and Cancel. These are hidden in ACT and respond only to the base
INF+1, INF+2 and INF+3 respectively. The base INF (Information Number)
parameter is an IEC 60870-5-103 identifier that associates a function in a 103
Master (such as Scada) with its equivalent in the IED.

Identification

Function description
IED commands with position and select
for IEC 60870-5-103
Function block
I103POSCMD
BLOCK
POSITION
SELECT
IEC10000286-1-en.vsd
IEC10000286 V1 EN-US
Figure 266:
I103POSCMD function block
Signals
Table 456:
I103POSCMD Input signals
Name
Type
BLOCK
BOOLEAN
POSITION
INTEGER
SELECT
BOOLEAN
Function block
IEC 60617
name
identification
I103POSCMD
-
Default
Description
0
Block of status reporting
0
Position of controllable object
0
Select of controllable object
1MRK 511 424-UEN B
GUID-ABF81C27-4605-4A15-9CF5-77FF82DE8747 v1
ANSI/IEEE C37.2
device number
-
GUID-3A31C1F2-1FB5-4DB0-A698-AD3F55738DB1 v1
PID-6997-INPUTSIGNALS v1
Bay control REC650 2.2 IEC
Technical manual