Signals - ABB Relion 650 Series Technical Manual

Bay control
Hide thumbs Also See for Relion 650 Series:
Table of Contents

Advertisement

Section 8
Control
8.3.8.3
236

Signals

Table 108:
SXSWI Input signals
Name
Type
BLOCK
BOOLEAN
LR_SWI
BOOLEAN
OPEN
BOOLEAN
CLOSE
BOOLEAN
BL_OPEN
BOOLEAN
BL_CLOSE
BOOLEAN
BL_UPD
BOOLEAN
POSOPEN
BOOLEAN
POSCLOSE
BOOLEAN
SWOPCAP
INTEGER
RS_CNT
BOOLEAN
EEH_WARN
BOOLEAN
EEH_ALM
BOOLEAN
XIN
GROUP
SIGNAL
Table 109:
SXSWI Output signals
Name
Type
XPOS
GROUP SIGNAL
EXE_OP
BOOLEAN
EXE_CL
BOOLEAN
SUBSTED
BOOLEAN
OP_BLKD
BOOLEAN
CL_BLKD
BOOLEAN
UPD_BLKD
BOOLEAN
POSITION
INTEGER
OPENPOS
BOOLEAN
CLOSEPOS
BOOLEAN
CNT_VAL
INTEGER
Table continues on next page
Default
Description
0
Block of function
0
Local/Remote switch indication from switchyard
0
Pulsed signal used to immediately open the
switch
0
Pulsed signal used to immediately close the
switch
0
Signal to block the open command
0
Signal to block the close command
0
Steady signal for block of the position updating
0
Signal for open position of apparatus from I/O
0
Signal for close position of apparatus from I/O
4
Switch operating capability 1 = None, 2 = O, 3 =
C, 4 = O and C
0
Resets the operation counter
0
Warning from external equipment
0
Alarm from external equipment
-
Execution information from CSWI
Description
Group connection to CSWI for XCBR and XSWI
Executes the command for open direction
Executes the command for close direction
Indication that the position is substituted
Indication that the function is blocked for open
commands
Indication that the function is blocked for close
commands
Update of position indication is blocked
Apparatus position indication
Apparatus open position
Apparatus closed position
Operation counter value
1MRK 511 424-UEN B
PID-6800-INPUTSIGNALS v4
PID-6800-OUTPUTSIGNALS v4
Bay control REC650 2.2 IEC
Technical manual