Section 13
Station communication
580
Table 466:
I103EF supported indications
INF
Description
51
Earth fault forward
52
Earth fault reverse
Autorecloser indications in monitor direction, I103AR
Indication block for autorecloser in monitor direction with defined functions.
Number of instances: 1
Function type is selected with parameter FunctionType.
Information number is defined for each output signal.
Table 467:
I103AR supported indications
INF
Description
16
Autorecloser active
128
CB on by Autorecloser
130
Autorecloser blocked
Function status fault protection for IEC 60870-5-103, I103FLTPROT
Number of instances: 1
Function type is selected with parameter FunctionType.
Information number is defined for each input signal.
Table 468:
I103FLTPROT supported functions
INF
Description
64
Start phase L1
65
Start phase L2
66
Start phase L3
67
Start residual current IN
68
Trip general
69
Trip phase L1
70
Trip phase L2
71
Trip phase L3
72
Back up trip I>>
73
Fault location in ohm
74
Forward/line
75
Reverse/busbar
76
Signal transmitted
77
Signal received
Table continues on next page
GUID-E9DF9410-F570-4F85-9063-C76D1D4A0668 v6
TYP
GI
COT
2
Y
1,7,9
2
Y
1,7,9
2
Y
1,7,9
2
Y
1,7,9
2
N
1,7
2
N
1,7
2
N
1,7
2
N
1,7
2
N
1,7
4
N
1,7
2
N
1,7
2
N
1,7
2
N
1,7
2
N
1,7
Bay control REC650 2.2 IEC
1MRK 511 424-UEN B
M11874-363 v6
Technical manual