Interlocking For Bus-Coupler Bay Abc_Bc - ABB Relion 650 Series Technical Manual

Bay control
Hide thumbs Also See for Relion 650 Series:
Table of Contents

Advertisement

Section 8
Control
8.2.7
8.2.7.1
162
Name
Type
S2QC2_OP
BOOLEAN
S2QC2_CL
BOOLEAN
S1DC_OP
BOOLEAN
S2DC_OP
BOOLEAN
VPS1_DC
BOOLEAN
VPS2_DC
BOOLEAN
EXDU_ES
BOOLEAN
EXDU_BB
BOOLEAN
QBCL_EX1
BOOLEAN
QBCL_EX2
BOOLEAN
QBOP_EX1
BOOLEAN
QBOP_EX2
BOOLEAN
QBOP_EX3
BOOLEAN
Table 71:
A1A2_DC Output signals
Name
Type
QBOPREL
BOOLEAN
QBOPITL
BOOLEAN
QBCLREL
BOOLEAN
QBCLITL
BOOLEAN
DCOPTR
BOOLEAN
DCCLTR
BOOLEAN
VPDCTR
BOOLEAN

Interlocking for bus-coupler bay ABC_BC

Identification
Function description
Interlocking for bus-coupler bay
Default
Description
0
QC2 on bus section 2 is in open position
0
QC2 on bus section 2 is in closed position
0
All disconnectors on bus section 1 are in open
position
0
All disconnectors on bus section 2 are in open
position
0
Switch status of disconnectors on bus section 1
are valid
0
Switch status of disconnectors on bus section 2
are valid
0
No transm error from bays containing earth. sw.
QC1 or QC2
0
No transm error from bays with disc conn to
section 1 and 2
0
External close condition for section disconnector
QB
0
External close condition for section disconnector
QB
0
External open condition for section disconnector
QB
0
External open condition for section disconnector
QB
0
External open condition for section disconnector
QB
Description
Opening of QB is allowed
Opening of QB is forbidden
Closing of QB is allowed
Closing of QB is forbidden
The bus section disconnector is in open position
The bus section disconnector is in closed position
Switch status of QB is valid (open or closed)
IEC 61850
IEC 60617
identification
identification
ABC_BC
-
1MRK 511 424-UEN B
PID-3499-OUTPUTSIGNALS v10
IP14144-1 v2
GUID-8149EE0A-E2A4-431C-9D07-D1A0BD296743 v3
ANSI/IEEE C37.2
device number
3
Bay control REC650 2.2 IEC
Technical manual

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rec650

Table of Contents