1MRK 511 424-UEN B
11.2.6
11.2.7
Bay control REC650 2.2 IEC
Technical manual

Monitored data

Table 368:
ETPMMTR Monitored data
Name
Type
EAFACC
REAL
EARACC
REAL
ERFACC
REAL
ERRACC
REAL
MAXPAFD
REAL
MAXPARD
REAL
MAXPRFD
REAL
MAXPRRD
REAL
Operation principle
The instantaneous output values of active and reactive power from the
Measurements function CVMMXN are used and integrated over a selected time
tEnergy to measure the integrated energy. Figure
functionality of the energy calculation and demand handling function ETPMMTR.
Values (Range)
Unit
-
MWh
-
MWh
-
MVArh
-
MVArh
-
MW
-
MW
-
MVAr
-
MVAr
222
shows the overall
Section 11
Metering
PID-6872-MONITOREDDATA v3
Description
Accumulated forward
active energy value
Accumulated reverse
active energy value
Accumulated forward
reactive energy value
Accumulated reverse
reactive energy value
Maximum forward active
power demand value for
set interval
Maximum reverse active
power demand value for
set interval
Maximum forward
reactive power demand
value for set interval
Maximum reverse
reactive power demand
value for set interval
GUID-4A46757C-EC5D-4BCE-9D09-C8152B062CE1 v3