ABB Relion 650 Series Technical Manual page 609

Bay control
Hide thumbs Also See for Relion 650 Series:
Table of Contents

Advertisement

1MRK 511 424-UEN B
Bay control REC650 2.2 IEC
Technical manual
Normal micro-processor watchdog function.
Checking of digitized measuring signals.
Other alarms, for example hardware and time synchronization.
The self-supervision function status can be monitored from the local HMI or from
the Event Viewer in PCM600.
Under the Diagnostics menu in the local HMI, the actual information from the self-
supervision function can be reviewed. The information can be found under Main
menu/Diagnostics/Internal events or Main menu/Diagnostics/IED status/
General. The information from the self-supervision function is also available in the
Event Viewer in PCM600.
IEC15000414 V2 EN-US
Figure 273:
IED general status in local HM
The self supervision records internal signal changes in an internal event list. A
maximum of 40 internal events are stored in a first-in, first-out manner.
GUID-B481701F-05B4-4B29-83D4-18F13886FEBE V1 EN-US
Figure 274:
Self-supervision event list in local HMI
A self-supervision summary can be obtained by means of an output relay with
potential free alarm contact (INTERNAL FAIL) located on the power supply
IEC15000414-2-en.vsdx