Technical Data - ABB Relion 650 Series Technical Manual

Bay control
Hide thumbs Also See for Relion 650 Series:
Table of Contents

Advertisement

Section 7
Secondary system supervision
7.1.7
7.2
7.2.1
114
| åI
| - | I
|
phase
ref
I
MinOp
IEC99000068 V1 EN-US
Figure 46:
Operate characteristics
Due to the formulas for the axis compared, |SIphase | - |I ref | and |S
I phase | + | I ref | respectively, the slope can not be above 1.

Technical data

Table 49:
CCSSPVCtechnical data
Function
Operate current
Reset ratio, Operate current
Block current
Reset ratio, Block current
Fuse failure supervision FUFSPVC
Identification
Function description
Fuse failure supervision
Slope = 1
Slope = 0.8
| åI
Range or value
(10-200)% of IBase
>90%
(20-500)% of IBase
>90% at (50-500)% of IBase
IEC 61850
IEC 60617
identification
identification
FUFSPVC
-
1MRK 511 424-UEN B
Operation
area
| + | I
|
phase
ref
99000068.vsd
M12358-1 v10
Accuracy
±10.0% of I
at I ≤ I
r
r
±10.0% of I at I > I
r
±5.0% of I
at I ≤ I
r
r
±5.0% of I at I > I
r
IP14556-1 v3
M14869-1 v4
ANSI/IEEE C37.2
device number
-
Bay control REC650 2.2 IEC
Technical manual