Section 8
Control
240
OPENPOS
CLOSEPOS
EXE_CL
EXE_CL
IEC05000098 V1 EN-US
Figure 106:
Execute output pulse
If the pulse is set to be adaptive, it is not possible for the pulse to exceed
tOpenPulse or tClosePulse.
The execute output pulses are reset when:
the new expected final position is reached and the configuration parameter
AdaptivePulse is set to true
the timer tOpenPulse or tClosePulse has elapsed
an error occurs due to the switch does not start moving, that is, tStartMove has
elapsed.
If the controlled primary device reaches the final position before the
execution pulse time has elapsed, and AdaptivePulse is not true, the
function waits for the end of the execution pulse before telling the
activating function that the command is completed.
There is one exception from the first item above. If the primary device is in open
position and an open command is executed or if the primary device is in close
position and a close command is executed. In these cases, with the additional
condition that the configuration parameter AdaptivePulse is true, the execute output
pulse is always activated and resets when tStartMove has elapsed. If the
configuration parameter AdaptivePulse is set to false the execution output remains
active until the pulse duration timer has elapsed.
If the start position indicates bad state (OPENPOS=1 and
CLOSEPOS =1) when a command is executed the execute output
pulse resets only when timer tOpenPulse or tClosePulse has
elapsed.
An example when a primary device is open and an open command is executed is
shown in Figure 107.
tClosePulse
tClosePulse
1MRK 511 424-UEN B
AdaptivePulse=FALSE
AdaptivePulse=TRUE
en05000098.vsd
Bay control REC650 2.2 IEC
Technical manual