Section 8
Control
212
Internal Cause
AddCause in IEC 61850-8-1
Number
Ed 2
24
24
26
26
27
27
-22
0
-23
24
-24
9
-25
9
-30
16
-31
16
-32
4
-33
22
-34
4
-35
22
Table 92:
Cause values not reflected on the output L_CAUSE
Cause number
Cause description
3
Select-failed
8
Blocked-by-Mode
12
Command-already-in-execution
13
Blocked-by-health
16
Time-limit-over
18
Object-not-selected
19
Object-already-selected
20
No-access-authority
26
Inconsistent-parameters
27
Locked-by-other-client
Name
Ed 1
-23
Blocked-by-command
6
Inconsistent-parameters
12
Locked-by-other-client
-22
Wrong-Ctl-model
-23
Blocked-by-command
-24
Blocked-for-open-cmd
-25
Blocked-for-close-cmd
-30
Long-operation-time
-31
Switch-not-start-moving
-32
Persistent-intermediate-state
-33
Switch-returned-to-init-pos
-34
Switch-in-bad-state
-35
Not-expected-final-position
Conditions
Canceled due to an unsuccessful selection
(select service)
Control action is blocked because the LN
(CSWI) is in a mode (Mod) which doesn't
allow any switching or does not match the
mode of the command.
Control, select or cancel service is rejected
because control action is already running.
Control action is blocked due to some
internal event that prevents a successful
operation (Health).
Control action is terminated due to exceed
of some time limit.
Control action is rejected because control
object was not selected.
Select action is not executed because the
addressed object is already selected.
Control action is blocked due to lack of
access authority.
The parameters between successive
control services are not consistent, for
ctlNum of Select and Operate
example the
service are different.
Another client has already reserved the
object.
1MRK 511 424-UEN B
Bay control REC650 2.2 IEC
Technical manual