Settings - ABB Relion 650 Series Technical Manual

Bay control
Hide thumbs Also See for Relion 650 Series:
Table of Contents

Advertisement

1MRK 511 424-UEN B
8.3.8.4
Table 110:
SXSWI Non group settings (basic)
Name
Values (Range)
tStartMove
tIntermediate
AdaptivePulse
tOpenPulse
tClosePulse
SwitchType
InitialCount
8.3.8.5
Bay control REC650 2.2 IEC
Technical manual
Name
L_CAUSE
EEHEALTH
SWOPCAP

Settings

Unit
0.000 - 60.000
s
0.000 - 60.000
s
Not adaptive
-
Adaptive
0.000 - 60.000
s
0.000 - 60.000
s
Load Break
-
Disconnector
Earthing Switch
HS Earthing Switch
0 - 20000
-
Operation principle
The users of the Circuit switch (SXSWI) are other functions such as for example,
switch controller, protection functions, autorecloser function, or a 61850 client
residing in another IED or the operator place. SXSWI executes commands,
evaluates block conditions and evaluates different time supervision conditions.
Only if all conditions indicate a switch operation to be allowed, SXSWI performs
the execution command. In case of erroneous conditions, the function indicates an
appropriate "cause" value, see Table 90.
SXSWI has an operation counter for closing and opening commands. The counter
value can be read remotely from the operator place. The value is reset from a
binary input or remotely from the operator place by configuring a signal from the
Single Point Generic Control 8 signals (SPC8GAPC), for example.
Also, the health of the external equipment, the switch, can be monitored according
to IEC 61850-8-1.
Local/Remote switch
One binary input signal LR_SWI is included in SXSWI to indicate the local/remote
switch position from switchyard provided via the I/O board. If this signal is set to
Type
Description
INTEGER
Latest value of the error indication during
command
INTEGER
External equipment health. 1=No warning or
alarm, 2=Warning, 3=Alarm
INTEGER
Switch operating capability 1 = None, 2 = O, 3 =
C, 4 = O and C
Step
Default
0.001
3.000
0.001
15.000
-
Not adaptive
0.001
0.200
0.001
0.200
-
Disconnector
1
0
Section 8
Description
Supervision time for the apparatus to
move after a command
Allowed time for intermediate position
Output resets when a new correct end
position is reached
Output pulse length for open command
Output pulse length for close command
1=LoadBreak,2=Disconnector,
3=EarthSw,4=HighSpeedEarthSw
Initial number of operations (Initial count
value)
Control
PID-6800-SETTINGS v4
M16494-3 v8
M16494-6 v4
237