Signals - ABB Relion 650 Series Technical Manual

Bay control
Hide thumbs Also See for Relion 650 Series:
Table of Contents

Advertisement

1MRK 511 424-UEN B
13.7.10.4
13.7.10.5
Table 446:
I103CMD Non group settings (basic)
Name
Values (Range)
FunctionType
13.7.11
13.7.11.1
13.7.11.2
Bay control REC650 2.2 IEC
Technical manual

Signals

Table 444:
I103CMD Input signals
Name
BLOCK
Table 445:
I103CMD Output signals
Name
16-AR
17-DIFF
18-PROT
Settings
Unit
1 - 255
-
IED commands for IEC 60870-5-103 I103IEDCMD
Functionality
I103IEDCMD is a command block in control direction with defined IED functions.
All outputs are pulsed and they are NOT stored. Pulse length is fixed to 400ms.
Identification
Function description
IED commands for IEC 60870-5-103
Type
Default
Description
BOOLEAN
0
Block of commands
Type
Description
BOOLEAN
Information number 16, off/on of autorecloser
BOOLEAN
Information number 17, block of differential
protection
BOOLEAN
Information number 18, block of protection
Step
Default
1
1
Function block
name
I103IEDCMD
Section 13
Station communication
PID-3969-INPUTSIGNALS v5
PID-3969-OUTPUTSIGNALS v5
Description
Function type (1-255)
GUID-19AD44B2-21D6-4DB0-AD74-1578DA30C100 v5
GUID-0D0B2477-1B0C-48F3-B047-CCF9C7A71856 v1
IEC 60617
ANSI/IEEE C37.2
identification
device number
-
-
PID-3969-SETTINGS v5