1MRK 511 424-UEN B
8.3.11.3
Bay control REC650 2.2 IEC
Technical manual
RESIN2
EXCH_IN
ACK_F_B
BAY_ACK
ANY_ACK
BAY_VAL
VALID_TX
BAY_RES
RE_RQ_B
V_RE_RQ
EXCH_OUT
IEC09000807_1_en.vsd
IEC09000807 V1 EN-US
Figure 112:
RESIN2 function block

Signals

Table 118:
RESIN1 Input signals
Name
Type
BAY_ACK
BOOLEAN
BAY_VAL
BOOLEAN
BAY_RES
BOOLEAN
Table 119:
RESIN1 Output signals
Name
Type
ACK_F_B
BOOLEAN
ANY_ACK
BOOLEAN
VALID_TX
BOOLEAN
RE_RQ_B
BOOLEAN
V_RE_RQ
BOOLEAN
EXCH_OUT
INTEGER
Table 120:
RESIN2 Input signals
Name
Type
EXCH_IN
INTEGER
BAY_ACK
BOOLEAN
BAY_VAL
BOOLEAN
BAY_RES
BOOLEAN
Default
Description
0
Another bay has acknow. the reservation req.
from this bay
0
The reserv. and acknow. signals from another
bay are valid
0
Request from other bay to reserve this bay
Description
All other bays have acknow. the reserv. req. from
this bay
Any other bay has acknow. the reserv. req. from
this bay
The reserv. and acknow. signals from other bays
are valid
Request from other bay to reserve this bay
Check if the request of reserving this bay is valid
Used for exchange signals between different
ResIn blocks
Default
Description
5
Used for exchange signals between different
ResIn blocks
0
Another bay has acknow. the reservation req.
from this bay
0
The reserv. and acknow. signals from another
bay are valid
0
Request from other bay to reserve this bay
Section 8
Control
PID-3629-INPUTSIGNALS v7
PID-3629-OUTPUTSIGNALS v7
PID-3630-INPUTSIGNALS v7