Settings - ABB Relion 650 Series Technical Manual

Bay control
Hide thumbs Also See for Relion 650 Series:
Table of Contents

Advertisement

Section 6
Multipurpose protection
6.1.5
Table 35:
CVGAPC Group settings (basic)
Name
Operation
CurrentInput
VoltageInput
OperHarmRestr
l_2nd/l_fund
BlkLevel2nd
EnRestrainCurr
RestrCurrInput
RestrCurrCoeff
RCADir
ROADir
LowVolt_VM
Operation_OC1
Table continues on next page
86

Settings

Values (Range)
Unit
Off
-
On
phase1
-
phase2
phase3
PosSeq
NegSeq
3*ZeroSeq
MaxPh
MinPh
UnbalancePh
phase1-phase2
phase2-phase3
phase3-phase1
MaxPh-Ph
MinPh-Ph
UnbalancePh-Ph
phase1
-
phase2
phase3
PosSeq
-NegSeq
-3*ZeroSeq
MaxPh
MinPh
UnbalancePh
phase1-phase2
phase2-phase3
phase3-phase1
MaxPh-Ph
MinPh-Ph
UnbalancePh-Ph
Off
-
On
10.0 - 50.0
%
10 - 5000
%IB
Off
-
On
PosSeq
-
NegSeq
3*ZeroSeq
Max
0.00 - 5.00
-
-180 - 180
Deg
1 - 90
Deg
0.0 - 5.0
%UB
Off
-
On
Step
Default
-
Off
-
MaxPh
-
MaxPh
-
Off
1.0
20.0
1
5000
-
Off
-
PosSeq
0.01
0.00
1
-75
1
75
0.1
0.5
-
Off
1MRK 511 424-UEN B
Description
Operation Off / On
Select current signal which will be
measured inside function
Select voltage signal which will be
measured inside function
Operation of 2nd harmonic restrain Off /
On
Ratio of second to fundamental current
harmonic in %
Harm analyse disabled above this
current level in % of fundamental current
Enable current restrain function On / Off
Select current signal which will be used
for curr restrain
Restraining current coefficient
Relay Characteristic Angle
Relay Operate Angle
Below this level in % of UBase setting
ActLowVolt takes over
Operation OC1 Off / On
Bay control REC650 2.2 IEC
Technical manual
PID-3857-SETTINGS v9