Section 11
Metering
11.1.4
11.1.5
Table 361:
PCFCNT Non group settings (basic)
Name
Operation
EventMask
CountCriteria
Scale
Quantity
tReporting
460

Signals

Table 359:
PCFCNT Input signals
Name
BI_PULSE
BLOCK
READ_VAL
RS_CNT
Table 360:
PCFCNT Output signals
Name
INVALID
RESTART
BLOCKED
NEW_VAL
SCAL_VAL
Settings
Values (Range)
Unit
Off
-
On
NoEvents
-
ReportEvents
Off
-
RisingEdge
Falling edge
OnChange
1.000 - 90000.000
-
Count
-
ActivePower
ApparentPower
ReactivePower
ActiveEnergy
ApparentEnergy
ReactiveEnergy
0 - 3600
s
Type
Default
Description
BOOLEAN
0
Connect binary input channel for metering
BOOLEAN
0
Block of function
BOOLEAN
0
Initiates an additional pulse counter reading
BOOLEAN
0
Resets pulse counter value
Type
Description
BOOLEAN
The pulse counter value is invalid
BOOLEAN
The reported value does not comprise a complete
integration cycle
BOOLEAN
The pulse counter function is blocked
BOOLEAN
A new pulse counter value is generated
REAL
Scaled value with time and status information
Step
Default
-
Off
-
NoEvents
-
RisingEdge
0.001
1.000
-
Count
1
60
1MRK 511 424-UEN B
PID-6509-INPUTSIGNALS v4
PID-6509-OUTPUTSIGNALS v4
Description
Operation Off/On
Report mask for analog events from
pulse counter
Pulse counter criteria
Scaling value for SCAL_VAL output to
unit per counted value
Measured quantity for SCAL_VAL output
Cycle time for reporting of counter value
Bay control REC650 2.2 IEC
Technical manual
PID-6509-SETTINGS v4