Section 9
Logic
9.8.4
9.8.4.1
9.8.4.2
316

Invalid logic function block INVALIDQT

Component which sets quality invalid of outputs according to a "valid" input.
The values of the input signals INPUTx (where 1<x<16) are copied to the outputs
OUTPUTx (where 1<x<16). If the input VALID is 0 or if its quality bit is set
invalid, all outputs OUTPUTx (where 1<x<16) quality bit will be set to invalid.
The time stamp of any output OUTPUTx (where 1<x<16) will be set to the latest
time stamp of any input and the input VALID.
INVALIDQT can propagate the quality, the value and the time stamps of the
signals via IEC 61850.
Function block
INVALIDQT
INPUT1
OUTPUT1
INPUT2
OUTPUT2
INPUT3
OUTPUT3
INPUT4
OUTPUT4
INPUT5
OUTPUT5
INPUT6
OUTPUT6
INPUT7
OUTPUT7
INPUT8
OUTPUT8
INPUT9
OUTPUT9
INPUT10
OUTPUT10
INPUT11
OUTPUT11
INPUT12
OUTPUT12
INPUT13
OUTPUT13
INPUT14
OUTPUT14
INPUT15
OUTPUT15
INPUT16
OUTPUT16
VALID
iec08000169.vsd
IEC08000169 V1 EN-US
Figure 152:
INVALIDQT function block
Signals
Table 214:
INVALIDQT Input signals
Name
Type
INPUT1
BOOLEAN
INPUT2
BOOLEAN
INPUT3
BOOLEAN
INPUT4
BOOLEAN
INPUT5
BOOLEAN
INPUT6
BOOLEAN
INPUT7
BOOLEAN
INPUT8
BOOLEAN
Table continues on next page
Default
Description
0
Indication input 1
0
Indication input 2
0
Indication input 3
0
Indication input 4
0
Indication input 5
0
Indication input 6
0
Indication input 7
0
Indication input 8
1MRK 511 424-UEN B
GUID-66C6DCEE-1F0E-4EB8-9ADB-97F8B41E53DF v4
GUID-0BD84306-0965-4702-8D5C-9570A70168EA v1
GUID-4543C4C9-FAE2-4328-8DE2-4A5756A020E9 v1
PID-3822-INPUTSIGNALS v5
Bay control REC650 2.2 IEC
Technical manual