ABB Relion 650 Series Technical Manual page 381

Bay control
Hide thumbs Also See for Relion 650 Series:
Table of Contents

Advertisement

1MRK 511 424-UEN B
Y
Value Reported
(1st)
(*)Set value for t: XDbRepInt
IEC05000500 V2 EN-US
Figure 178:
Periodic reporting
Bay control REC650 2.2 IEC
Technical manual
Value Reported
Y2
Y1
t (*)
Amplitude dead-band supervision
If a measuring value is changed, compared to the last reported value, and the
change is larger than the ±ΔY pre-defined limits that are set by user (XDbRepInt),
then the measuring channel reports the new value to a higher level. This limits the
information flow to a minimum necessary. Figure
amplitude dead-band supervision. The picture is simplified: the process is not
continuous but the values are evaluated with a time interval of one execution cycle
from each other.
Value Reported
Y3
Y4
t (*)
t (*)
Section 10
Monitoring
Value Reported
Value Reported
Y5
t (*)
IEC05000500-2-en.vsdx
179
shows an example with the
t
SEMOD54417-163 v6
375