ABB Relion 650 Series Technical Manual page 98

Bay control
Hide thumbs Also See for Relion 650 Series:
Table of Contents

Advertisement

Section 6
Multipurpose protection
Name
ResCrvType_OV2
tResetDef_OV2
tResetIDMT_OV2
A_OV2
B_OV2
C_OV2
D_OV2
P_OV2
ResCrvType_UV1
tResetDef_UV1
tResetIDMT_UV1
A_UV1
B_UV1
C_UV1
D_UV1
P_UV1
ResCrvType_UV2
tResetDef_UV2
tResetIDMT_UV2
A_UV2
B_UV2
C_UV2
D_UV2
P_UV2
92
Values (Range)
Unit
Instantaneous
-
Frozen timer
Linearly decreased
0.00 - 6000.00
s
0.00 - 6000.00
s
0.005 - 999.000
-
0.500 - 99.000
-
0.000 - 1.000
-
0.000 - 10.000
-
0.001 - 10.000
-
Instantaneous
-
Frozen timer
Linearly decreased
0.00 - 6000.00
s
0.00 - 6000.00
s
0.005 - 999.000
-
0.500 - 99.000
-
0.000 - 1.000
-
0.000 - 10.000
-
0.001 - 10.000
-
Instantaneous
-
Frozen timer
Linearly decreased
0.00 - 6000.00
s
0.00 - 6000.00
s
0.005 - 999.000
-
0.500 - 99.000
-
0.000 - 1.000
-
0.000 - 10.000
-
0.001 - 10.000
-
Step
Default
-
Instantaneous
0.01
0.00
0.01
0.00
0.001
0.140
0.001
1.000
0.001
1.000
0.001
0.000
0.001
0.020
-
Instantaneous
0.01
0.00
0.01
0.00
0.001
0.140
0.001
1.000
0.001
1.000
0.001
0.000
0.001
0.020
-
Instantaneous
0.01
0.00
0.01
0.00
0.001
0.140
0.001
1.000
0.001
1.000
0.001
0.000
0.001
0.020
1MRK 511 424-UEN B
Description
Selection of reset curve type for OV2
Reset time delay in sec for definite time
use of OV2
Reset time delay in sec for IDMT curves
for OV2
Parameter A for customer programmable
curve for OV2
Parameter B for customer programmable
curve for OV2
Parameter C for customer
programmable curve for OV2
Parameter D for customer
programmable curve for OV2
Parameter P for customer programmable
curve for OV2
Selection of reset curve type for UV1
Reset time delay in sec for definite time
use of UV1
Reset time delay in sec for IDMT curves
for UV1
Parameter A for customer programmable
curve for UV1
Parameter B for customer programmable
curve for UV1
Parameter C for customer
programmable curve for UV1
Parameter D for customer
programmable curve for UV1
Parameter P for customer programmable
curve for UV1
Selection of reset curve type for UV2
Reset time delay in sec for definite time
use of UV2
Reset time delay in sec for IDMT curves
for UV2
Parameter A for customer programmable
curve for UV2
Parameter B for customer programmable
curve for UV2
Parameter C for customer
programmable curve for UV2
Parameter D for customer
programmable curve for UV2
Parameter P for customer programmable
curve for UV2
Bay control REC650 2.2 IEC