Goosexlnrcv - ABB Relion 650 Series Technical Manual

Bay control
Hide thumbs Also See for Relion 650 Series:
Table of Contents

Advertisement

1MRK 511 424-UEN B
13.3.13
13.3.13.1
13.3.13.2
Bay control REC650 2.2 IEC
Technical manual
Incoming data with q=test+oldData
Receiver in block
Receiver in block and
communication error
Receiver in test mode and incoming
data with q= Normal
Receiver in test mode and incoming
data with q= Test
Communication Error
At least one of the inputs of this GOOSE block must be linked
either in SMT by means of a cross or in ACT by means of a
GOOSE connection (if easy GOOSE engineering is enabled) to
receive any data. Only those outputs whose source input is linked/
connected will be updated.
The implementation for IEC 61850 quality data handling is
restricted to a simple level. If quality data validity is GOOD then
the DVALIDx output will be HIGH. If quality data validity is
INVALID, QUESTIONABLE, OVERFLOW, FAILURE or OLD
DATA then the DVALIDx output will be LOW.
GOOSE function block to receive a switching device

GOOSEXLNRCV

Identification
Function description
GOOSE function block to receive a
switching device
Functionality
The GOOSE XLN Receive component is used to collect information from another
device's XCBR/XSWI logical node sent over process bus via GOOSE. The
GOOSE XLN Receive component includes 12 different outputs (and their
respective channel valid bits) with defined names to ease the 61850 mapping of the
GOOSE signals in the configuration process.
Station communication
Data Value
Data Valid
0
0
0
0
0
0
Updated
1
Updated
1
0
0
IEC 61850
IEC 60617
identification
identification
GOOSEXLNRCV
-
Section 13
Comm Valid
Test
1
1
1
0
0
0
1
0
1
1
0
0
GUID-4B23D0CF-F298-4BBC-B833-1B8CC98D1604 v1
ANSI/IEEE C37.2
device number
-
GUID-5AC7DE11-CB95-4565-A8AE-FB23D59FD717 v1
511