1MRK 511 424-UEN B
13.7.14.5
Table 457:
I103POSCMD Non group settings (basic)
Name
Values (Range)
FunctionType
InfNo
13.7.15
13.7.15.1
13.7.15.2
13.7.15.3
Bay control REC650 2.2 IEC
Technical manual

Settings

Unit
1 - 255
-
160 - 236
-
IED commands with position for IEC 60870-5-103
I103POSCMDV
Functionality
I103POSCMDV is a transceiver function that monitors activity on its input signals
and interprets any state transition into commands sent over an established IEC
60870-5-103 link. Additionally, it listens for general interrogation (GI) requests,
and replies to those with a GI response message with the current state of each
connected input.
Input POSITION is a double-indication signal, and it is GI enabled. This means
that any state transition, that is to ON, OFF, intermediate and faulty, is reported
spontaneously. However, the intermediate and faulty states may be suppressed by
setting the Report Intermediate Position = Off. See the settings for RS485 and
optical serial communication for more information.
When input BLOCK is ON, the function ignores GI requests and ceases all
monitoring activity. Consequently, no transitions will be detected.
Identification
Function description
IED direct commands with position for
IEC 60870-5-103
Function block
I103POSCMDV
BLOCK
POSITION
IEC15000081-2-en.vsdx
IEC15000081 V2 EN-US
Figure 267:
I103POSCMDV function block
Step
Default
1
1
4
160
Function block
name
I103POSCMDV
Section 13
Station communication
Description
Function type
Information number for command output
GUID-CF04D9AC-40BE-46A3-A418-77204D2B0F27 v3
GUID-2249B679-03E4-43CC-B690-916246FE6A31 v1
IEC 60617
ANSI/IEEE C37.2
identification
device number
-
-
GUID-031C0F49-BEBD-40FE-A33F-18F1D94BB4B0 v1
PID-6997-SETTINGS v1
575