1MRK 511 424-UEN B
15.8.3
Bay control REC650 2.2 IEC
Technical manual
n=1–12 in task group 1
n=13–24 in task group 2
n=25–36 in task group 3
The task time defines the execution repetition rate, and is 1, 3 or 8 respectively for
the three task time groups.
SMAI2
BLOCK
G2AI3P
REVROT
G2AI1
^GRP2L1
G2AI2
^GRP2L2
G2AI3
^GRP2L3
G2AI4
^GRP2N
G2N
IEC14000028-1-en.vsd
IEC14000028 V1 EN-US
Figure 286:
SMAI2 function block
Figure
286
is an example of SMAI2:n to SMAI12:m in each of the three task time
groups 1, 2 or 3 where:
n=2 and m=12 in task group 1
n=14 and m=24 in task group 2
n=26 and m=36 in task group 3
The task time defines the execution repetition rate and is 3, 8 or 1 ms, respectively,
for the three task time groups.

Signals

Table 512:
SMAI1 Input signals
Name
Type
BLOCK
BOOLEAN
DFTSPFC
REAL
REVROT
BOOLEAN
GRP1L1
STRING
GRP1L2
STRING
GRP1L3
STRING
GRP1N
STRING
Basic IED functions
Default
Description
0
Block group 1
20.0
Number of samples per fundamental cycle used
for DFT calculation
0
Reverse rotation group 1
-
First analog input used for phase L1 or L1-L2
quantity
-
Second analog input used for phase L2 or L2-L3
quantity
-
Third analog input used for phase L3 or L3-L1
quantity
-
Fourth analog input used for residual or neutral
quantity
Section 15
SEMOD54997-4 v10
SEMOD55773-1 v2
PID-3405-INPUTSIGNALS v6
637