Function Block - ABB Relion 650 Series Technical Manual

Bay control
Hide thumbs Also See for Relion 650 Series:
Table of Contents

Advertisement

1MRK 511 424-UEN B
8.2.3.3
8.2.3.4
8.2.3.5
Bay control REC650 2.2 IEC
Technical manual

Function block

SCILO
POSOPEN
EN_OPEN
POSCLOSE
EN_CLOSE
OPEN_EN
CLOSE_EN
IEC05000359-2-en.vsd
IEC05000359 V2 EN-US
Figure 64:
SCILO function block
Signals
Table 64:
SCILO Input signals
Name
Type
POSOPEN
BOOLEAN
POSCLOSE
BOOLEAN
OPEN_EN
BOOLEAN
CLOSE_EN
BOOLEAN
Table 65:
SCILO Output signals
Name
Type
EN_OPEN
BOOLEAN
EN_CLOSE
BOOLEAN
Logic diagram
The function contains logic to enable the open and close commands respectively if
the interlocking conditions are fulfilled. That means also, if the switch has a
defined end position for example, open, then the appropriate enable signal (in this
case EN_OPEN) is false. The enable signals EN_OPEN and EN_CLOSE can be
true at the same time only in the intermediate and bad position state and if they are
enabled by the interlocking function. The position inputs come from the logical
nodes Circuit breaker/Circuit switch (SXCBR/SXSWI) and the enable signals
come from the interlocking logic. The outputs are connected to the logical node
Switch controller (SCSWI). One instance per switching device is needed.
Default
Description
0
Open position of switch device
0
Closed position of switch device
0
Open operation from interlocking logic is enabled
0
Close operation from interlocking logic is enabled
Description
Open operation at closed or interm. or bad pos. is
enabled
Close operation at open or interm. or bad pos. is
enabled
Section 8
Control
M15049-3 v6
PID-3487-INPUTSIGNALS v7
PID-3487-OUTPUTSIGNALS v7
M15086-3 v6
153