Section 9
DNP3 communication engineering
9.2
130

Adding setting groups

In order to show for a DNP master which setting group is used, the following
procedure can be performed.
In this example, only setting groups one and two are used. The DNP3 master will get
two binary inputs: the first is set if setting group one is used, the second is set if setting
group two is used.
1.
Configure ACTVGRP (Basic IED functions) and SPGGIO (Monitoring) with
the Application Configuration Tool (ACT).
GUID-E4A10C6E-40C8-4FD0-8A5A-BAEFCDDC4AE3 V1 EN
Figure 99:
Application configuration tool
To make it easier to recognize the signals for the active setting
group, the user-defined names are used.
2.
Open the Communication Management tool. Set Signal Type to Binary Input
Object and choose the connection of the master for which the values should be
presented.
1MRS756800 F
630 series
Engineering Manual