Technical Data - ABB Relion 650 Series Technical Manual

Bay control
Hide thumbs Also See for Relion 650 Series:
Table of Contents

Advertisement

1MRK 511 424-UEN B
11.1.8
11.2
11.2.1
11.2.2
Bay control REC650 2.2 IEC
Technical manual
The NEW_VAL signal is a pulse signal. The signal is set if the counter value was
updated since last report.
Note, the pulse is short, one cycle.
The SCAL_VAL signal consists of scaled value (according to parameter Scale),
time and status information.

Technical data

Table 363:
PCFCNT technical data
Function
Input frequency
Cycle time for report of
counter value
Function for energy calculation and demand
handling ETPMMTR
Identification
Function description
Function for energy calculation and
demand handling
Functionality
Power system measurement (CVMMXN) can be used to measure active as well as
reactive power values. Function for energy calculation and demand handling
(ETPMMTR) uses measured active and reactive power as input and calculates the
accumulated active and reactive energy pulses, in forward and reverse direction.
Energy values can be read or generated as pulses. Maximum demand power values
are also calculated by the function. This function includes zero point clamping to
remove noise from the input signal. As output of this function: periodic energy
calculations, integration of energy values, calculation of energy pulses, alarm
signals for limit violation of energy values and maximum power demand, can be
found.
Setting range
See Binary Input Module (BIM)
(1–3600) s
IEC 61850
IEC 60617
identification
identification
ETPMMTR
Section 11
Metering
IP14092-1 v1
M13404-2 v5
Accuracy
-
-
SEMOD153638-1 v2
SEMOD175537-2 v4
ANSI/IEEE C37.2
device number
W_Varh
-
GUID-6898E29B-DA70-421C-837C-1BBED8C63A7A v3
463