ABB Relion 650 Series Technical Manual page 175

Bay control
Hide thumbs Also See for Relion 650 Series:
Table of Contents

Advertisement

1MRK 511 424-UEN B
Bay control REC650 2.2 IEC
Technical manual
Name
Type
QA1CLITL
BOOLEAN
QB1REL
BOOLEAN
QB1ITL
BOOLEAN
QB2REL
BOOLEAN
QB2ITL
BOOLEAN
QB7REL
BOOLEAN
QB7ITL
BOOLEAN
QB20REL
BOOLEAN
QB20ITL
BOOLEAN
QC1REL
BOOLEAN
QC1ITL
BOOLEAN
QC2REL
BOOLEAN
QC2ITL
BOOLEAN
QB1OPTR
BOOLEAN
QB1CLTR
BOOLEAN
QB220OTR
BOOLEAN
QB220CTR
BOOLEAN
QB7OPTR
BOOLEAN
QB7CLTR
BOOLEAN
QB12OPTR
BOOLEAN
QB12CLTR
BOOLEAN
BC12OPTR
BOOLEAN
BC12CLTR
BOOLEAN
BC17OPTR
BOOLEAN
BC17CLTR
BOOLEAN
BC27OPTR
BOOLEAN
BC27CLTR
BOOLEAN
VPQB1TR
BOOLEAN
VQB220TR
BOOLEAN
VPQB7TR
BOOLEAN
VPQB12TR
BOOLEAN
VPBC12TR
BOOLEAN
VPBC17TR
BOOLEAN
VPBC27TR
BOOLEAN
Description
Closing of QA1 is forbidden
Switching of QB1 is allowed
Switching of QB1 is forbidden
Switching of QB2 is allowed
Switching of QB2 is forbidden
Switching of QB7 is allowed
Switching of QB7 is forbidden
Switching of QB20 is allowed
Switching of QB20 is forbidden
Switching of QC1 is allowed
Switching of QC1 is forbidden
Switching of QC2 is allowed
Switching of QC2 is forbidden
QB1 is in open position
QB1 is in closed position
QB2 and QB20 are in open position
QB2 or QB20 or both are not in open position
QB7 is in open position
QB7 is in closed position
QB1 or QB2 or both are in open position
QB1 and QB2 are not in open position
No connection via the own bus coupler between
WA1 and WA2
Conn. exists via the own bus coupler between
WA1 and WA2
No connection via the own bus coupler between
WA1 and WA7
Conn. exists via the own bus coupler between
WA1 and WA7
No connection via the own bus coupler between
WA2 and WA7
Conn. exists via the own bus coupler between
WA2 and WA7
Switch status of QB1 is valid (open or closed)
Switch status of QB2 and QB20 are valid (open
or closed)
Switch status of QB7 is valid (open or closed)
Switch status of QB1 and QB2 are valid (open or
closed)
Status of the bus coupler app. between WA1 and
WA2 are valid
Status of the bus coupler app. between WA1 and
WA7 are valid
Status of the bus coupler app. between WA2 and
WA7 are valid
Section 8
Control
169

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rec650

Table of Contents