Monitored Data - ABB Relion 650 Series Technical Manual

Bay control
Hide thumbs Also See for Relion 650 Series:
Table of Contents

Advertisement

1MRK 511 424-UEN B
Name
Values (Range)
SelPhaseLine1
SelPhaseLine2
CBConfig
Table 60:
SESRSYN Non group settings (advanced)
Name
Values (Range)
PhaseShift
8.1.6
8.1.7
8.1.7.1
Bay control REC650 2.2 IEC
Technical manual
Unit
Phase L1
-
Phase L2
Phase L3
Phase L1L2
Phase L2L3
Phase L3L1
Positive sequence
Phase L1
-
Phase L2
Phase L3
Phase L1L2
Phase L2L3
Phase L3L1
Positive sequence
No voltage sel.
-
Double bus
1 1/2 bus CB
1 1/2 bus alt. CB
Tie CB
Unit
-180 - 180
Deg

Monitored data

Table 61:
SESRSYN Monitored data
Name
UDIFFME
FRDIFFME
PHDIFFME
UBUS
ULINE
Operation principle
Basic functionality
The synchrocheck feature measures the conditions across the circuit breaker and
compares them to set limits. The output for closing operation is given when all
measured quantities are simultaneously within their set limits.
Step
Default
-
Phase L1
-
Phase L1
-
No voltage sel.
Step
Default
1
0
Type
Values (Range)
REAL
-
REAL
-
REAL
-
REAL
-
REAL
-
Section 8
Description
Select phase for line1
Select phase for line2
Select CB configuration
Description
Additional phase angle for selected line
voltage
PID-6724-MONITOREDDATA v1
Unit
Description
-
Calculated difference of
voltage in p.u of set
voltage base value
Hz
Calculated difference of
frequency
deg
Calculated difference of
phase angle
kV
Bus voltage
kV
Line voltage
Control
M14832-3 v8