ABB Relion 650 Series Technical Manual page 718

Bay control
Hide thumbs Also See for Relion 650 Series:
Table of Contents

Advertisement

Section 19
Inverse time characteristics
712
Table 576:
IEC Inverse time characteristics for Sensitive directional residual overcurrent and
power protection
Function
Operating characteristic:
æ
ö
A
ç
÷
=
×
t
k
(
)
ç
÷
P
è
-
ø
I
1
EQUATION1251-SMALL V1 EN-US
I = I
/I
measured
set
IEC Normal Inverse
IEC Very inverse
IEC Inverse
IEC Extremely inverse
IEC Short time inverse
IEC Long time inverse
Programmable characteristic
Operate characteristic:
æ
ö
A
ç
÷
=
+
×
t
B
k
(
)
ç
÷
P
è
-
ø
I
C
EQUATION1370-SMALL V1 EN-US
Reset characteristic:
TR
=
×
t
k
(
)
PR
-
I
CR
EQUATION1253-SMALL V1 EN-US
I = I
/I
measured
set
The parameter setting TimeChar = Reserved shall not be used, since
this parameter setting is for future use and not implemented yet.
Range or value
0.05 ≤ k ≤ 2.00
1.5 x I
≤ I ≤ 20 x I
set
set
A=0.14, P=0.02
A=13.5, P=1.0
A=0.14, P=0.02
A=80.0, P=2.0
A=0.05, P=0.04
A=120, P=1.0
k = (0.05-2.00) in steps of
0.01
A=(0.005-200.000) in steps of
0.001
B=(0.00-20.00) in steps of
0.01
C=(0.1-10.0) in steps of 0.1
P=(0.005-3.000) in steps of
0.001
TR=(0.005-100.000) in steps
of 0.001
CR=(0.1-10.0) in steps of 0.1
PR=(0.005-3.000) in steps of
0.001
1MRK 511 424-UEN B
Accuracy
IEC 60255-151, ±5.0%
or ±160 ms whichever
is greater
Bay control REC650 2.2 IEC
Technical manual