Function Block - ABB Relion 650 Series Technical Manual

Bay control
Hide thumbs Also See for Relion 650 Series:
Table of Contents

Advertisement

1MRK 511 424-UEN B
10.2.3
10.2.4
Bay control REC650 2.2 IEC
Technical manual

Function block

SSIMG
BLOCK
LOCKOUT
BLKALM
PRESLO
SENPRES
TEMPLO
SENTEMP
ALARM
SENPRESALM
PRESALM
SENPRESLO
TEMPALM
SETPLO
PRESSURE
SETTLO
TEMP
RESETLO
IEC09000129-2-en.vsdx
IEC09000129 V2 EN-US
Figure 184:
SSIMG function block
Signals
Table 311:
SSIMG Input signals
Name
Type
BLOCK
BOOLEAN
BLKALM
BOOLEAN
SENPRES
REAL
SENTEMP
REAL
SENPRESALM
BOOLEAN
SENPRESLO
BOOLEAN
SETPLO
BOOLEAN
SETTLO
BOOLEAN
RESETLO
BOOLEAN
Table 312:
SSIMG Output signals
Name
Type
LOCKOUT
BOOLEAN
PRESLO
BOOLEAN
TEMPLO
BOOLEAN
ALARM
BOOLEAN
PRESALM
BOOLEAN
TEMPALM
BOOLEAN
PRESSURE
REAL
TEMP
REAL
Default
Description
0
Block of function
0
Block all the alarms
0.0
Pressure input from CB
0.0
Temperature of the insulation medium from CB
0
Pressure alarm signal
0
Pressure lockout signal
0
Set pressure lockout
0
Set temperature lockout
0
Reset pressure and temperature lockout
Description
Pressure below lockout level or temperature
above lockout level
Pressure below lockout level
Temperature above lockout level
Pressure below alarm level or temperature above
alarm level
Pressure below alarm level
Temperature above alarm level
Pressure service value
Temperature of the insulation medium
Section 10
Monitoring
GUID-94B75A6D-973D-4F1F-8643-F2128AD31CC4 v3
GUID-89749F71-CAEB-4A57-A1F0-148CCF68E97E v2
PID-6950-INPUTSIGNALS v6
PID-6950-OUTPUTSIGNALS v6