ABB Relion 650 Series Technical Manual page 587

Bay control
Hide thumbs Also See for Relion 650 Series:
Table of Contents

Advertisement

1MRK 511 424-UEN B
Bay control REC650 2.2 IEC
Technical manual
INF
Description
78
Zone 1
79
Zone 2
80
Zone 3
81
Zone 4
82
Zone 5
83
Zone 6
84
Start general
85
Breaker failure
86
Trip measuring system phase L1
87
Trip measuring system phase L2
88
Trip measuring system phase L3
89
Trip measuring system neutral N
90
Over current trip, stage low
91
Over current trip, stage high
92
Earth-fault trip, stage low
93
Earth-fault trip, stage high
Measurands
Function blocks in monitor direction for input measurands. Typically connected to
monitoring function, for example to power measurement CVMMXN.
Measurands in public range, I103MEAS
Number of instances: 1
The IED reports all valid measuring types depending on connected signals.
Upper limit for measured currents, active/reactive-power is 2.4 times rated value.
Upper limit for measured voltages and frequency is 1.2 times rated value.
The upper limit is the maximum value that can be encoded into the ASDU
(Application Service Data Unit). Any value higher than this value will be tagged as
OVERFLOW. The factors 1.2 and 2.4 are taken from the 103 standard and require
that a rated value to use as base exists, and then use 1.2 or 2.4 times <rated> as
maxVal. You can use 2.4 times rated as maxVal, but as there is no way to propagate
value to client, the use of a scale factor on <rated> does not make much difference.
You can configure client:client-scaled-max ::= 1.2 * <rated> or
client-scaled-max ::= 1.0 * <maxVal>
If the client has a hard-coded gain of 1.2 * <rated> then client-scaled-
max ::= 1.2 times <maxVal>/1.2
Resolution is <maxVal> / 4095 and hence the lowest possible maxVal yields the
best accuracy.
Station communication
TYP
GI
COT
2
N
1,7
2
N
1,7
2
N
1,7
2
N
1,7
2
N
1,7
2
N
1,7
2
Y
1,7,9
2
N
1,7
2
N
1,7
2
N
1,7
2
N
1,7
2
N
1,7
2
N
1,7
2
N
1,7
2
N
1,7
2
N
1,7
Section 13
M11874-382 v2
M11874-385 v8
581