ABB Relion 650 Series Technical Manual page 368

Bay control
Hide thumbs Also See for Relion 650 Series:
Table of Contents

Advertisement

Section 10
Monitoring
Name
UAmpComp30
UAmpComp100
IAmpComp5
IAmpComp30
IAmpComp100
IAngComp5
IAngComp30
IAngComp100
Table 289:
CMMXU Non group settings (basic)
Name
IL1DbRepInt
Operation
IL1Min
IL1Max
GlobalBaseSel
IL1RepTyp
IL1AngDbRepInt
IL2DbRepInt
IL2Min
IL2Max
IL2RepTyp
IL2AngDbRepInt
IL3DbRepInt
IL3Min
Table continues on next page
362
Values (Range)
Unit
-10.000 - 10.000
%
-10.000 - 10.000
%
-10.000 - 10.000
%
-10.000 - 10.000
%
-10.000 - 10.000
%
-10.000 - 10.000
Deg
-10.000 - 10.000
Deg
-10.000 - 10.000
Deg
Values (Range)
Unit
1 - 100000
Type
Off
-
On
0.0 - 500.0
%IB
0.0 - 500.0
%IB
1 - 12
-
Cyclic
-
Deadband
Int deadband
Db & Cyclic 5s
Db & Cyclic 30s
Db & Cyclic 1min
1 - 100000
s
1 - 100000
Type
0.0 - 500.0
%IB
0.0 - 500.0
%IB
Cyclic
-
Deadband
Int deadband
Db & Cyclic 5s
Db & Cyclic 30s
Db & Cyclic 1min
1 - 100000
s
1 - 100000
Type
0.0 - 500.0
%IB
Step
Default
0.001
0.000
0.001
0.000
0.001
0.000
0.001
0.000
0.001
0.000
0.001
0.000
0.001
0.000
0.001
0.000
Step
Default
1
10
-
Off
0.1
50.0
0.1
200.0
1
1
-
Cyclic
1
10
1
10
0.1
50.0
0.1
200.0
-
Cyclic
1
10
1
10
0.1
50.0
1MRK 511 424-UEN B
Description
Amplitude factor to calibrate voltage at
30% of Ur
Amplitude factor to calibrate voltage at
100% of Ur
Amplitude factor to calibrate current at
5% of Ir
Amplitude factor to calibrate current at
30% of Ir
Amplitude factor to calibrate current at
100% of Ir
Angle calibration for current at 5% of Ir
Angle calibration for current at 30% of Ir
Angle calibration for current at 100% of Ir
Description
Cycl: Report interval (s), Db: In 0,001%
of range, Int Db: In 0,001%s
Operation Mode On / Off
Minimum value in % of IBase
Maximum value in % of IBase
Selection of one of the Global Base
Value groups
Reporting type
Cyclic report interval (s)
Cycl: Report interval (s), Db: In 0,001%
of range, Int Db: In 0,001%s
Minimum value in % of IBase
Maximum value in % of IBase
Reporting type
Cyclic report interval (s)
Cycl: Report interval (s), Db: In 0,001%
of range, Int Db: In 0,001%s
Minimum value in % of IBase
Bay control REC650 2.2 IEC
Technical manual
PID-6735-SETTINGS v3