ABB Relion 650 Series Technical Manual page 97

Bay control
Hide thumbs Also See for Relion 650 Series:
Table of Contents

Advertisement

1MRK 511 424-UEN B
Name
Values (Range)
C_OC1
PR_OC1
TR_OC1
CR_OC1
CurrMult_OC2
ResCrvType_OC2
tResetDef_OC2
P_OC2
A_OC2
B_OC2
C_OC2
PR_OC2
TR_OC2
CR_OC2
tResetDef_UC2
ResCrvType_OV1
tResetDef_OV1
tResetIDMT_OV1
A_OV1
B_OV1
C_OV1
D_OV1
P_OV1
Table continues on next page
Bay control REC650 2.2 IEC
Technical manual
Unit
0.000 - 1.000
-
0.005 - 3.000
-
0.005 - 600.000
-
0.1 - 10.0
-
1.0 - 10.0
-
Instantaneous
-
IEC Reset
ANSI reset
0.00 - 6000.00
s
0.001 - 10.000
-
0.000 - 999.000
-
0.000 - 99.000
-
0.000 - 1.000
-
0.005 - 3.000
-
0.005 - 600.000
-
0.1 - 10.0
-
0.00 - 6000.00
s
Instantaneous
-
Frozen timer
Linearly decreased
0.00 - 6000.00
s
0.00 - 6000.00
s
0.005 - 999.000
-
0.500 - 99.000
-
0.000 - 1.000
-
0.000 - 10.000
-
0.001 - 10.000
-
Step
Default
0.001
1.000
0.001
0.500
0.001
13.500
0.1
1.0
0.1
2.0
-
Instantaneous
0.01
0.00
0.001
0.020
0.001
0.140
0.001
0.000
0.001
1.000
0.001
0.500
0.001
13.500
0.1
1.0
0.01
0.00
-
Instantaneous
0.01
0.00
0.01
0.00
0.001
0.140
0.001
1.000
0.001
1.000
0.001
0.000
0.001
0.020
Section 6
Multipurpose protection
Description
Parameter C for customer
programmable curve for OC1
Parameter PR for customer
programmable curve for OC1
Parameter TR for customer
programmable curve for OC1
Parameter CR for customer
programmable curve for OC1
Multiplier for scaling the current setting
value for OC2
Selection of reset curve type for OC2
Reset time delay used in IEC Definite
Time curve OC2
Parameter P for customer programmable
curve for OC2
Parameter A for customer programmable
curve for OC2
Parameter B for customer programmable
curve for OC2
Parameter C for customer
programmable curve for OC2
Parameter PR for customer
programmable curve for OC2
Parameter TR for customer
programmable curve for OC2
Parameter CR for customer
programmable curve for OC2
Reset time delay used in IEC Definite
Time curve UC2
Selection of reset curve type for OV1
Reset time delay in sec for definite time
use of OV1
Reset time delay in sec for IDMT curves
for OV1
Parameter A for customer programmable
curve for OV1
Parameter B for customer programmable
curve for OV1
Parameter C for customer
programmable curve for OV1
Parameter D for customer
programmable curve for OV1
Parameter P for customer programmable
curve for OV1
91

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rec650