Goose Function Block To Receive An Integer Value Gooseintrcv - ABB Relion 650 Series Technical Manual

Bay control
Hide thumbs Also See for Relion 650 Series:
Table of Contents

Advertisement

1MRK 511 424-UEN B
13.3.8
13.3.8.1
13.3.8.2
13.3.8.3
Bay control REC650 2.2 IEC
Technical manual
Receiver in test mode and incoming
data with q= Normal
Receiver in test mode and incoming
data with q= Test
Communication Error
The input of this GOOSE block must be linked either in SMT by
means of a cross or in ACT by means of a GOOSE connection (if
easy GOOSE engineering is enabled) to receive the double point
values.
The implementation for IEC 61850 quality data handling is
restricted to a simple level. If quality data validity is GOOD then
the DATAVALID output will be HIGH. If quality data validity is
INVALID, QUESTIONABLE, OVERFLOW, FAILURE or OLD
DATA then the DATAVALID output will be LOW.
GOOSE function block to receive an integer value
GOOSEINTRCV
Identification
Function description
GOOSE function block to receive an
integer value
Functionality
GOOSEINTRCV is used to receive an integer value using IEC 61850 protocol via
GOOSE.
Function block
GOOSEINTRCV
BLOCK
^INTOUT
^SRCINTOUT
DATAVALID
COMMVALID
TEST
IEC10000250-2-en.vsd
IEC10000250 V2 EN-US
Figure 238:
GOOSEINTRCV function block
Station communication
Data Value
Data Valid
Updated
1
Updated
1
0
0
IEC 61850
IEC 60617
identification
identification
GOOSEINTRCV
-
Section 13
Comm Valid
Test
1
0
1
1
0
0
GUID-93A1E81B-1DE8-483A-BB3B-DB771EE66DC1 v1
ANSI/IEEE C37.2
device number
-
GUID-27B1ED7A-C8E8-499E-89C1-C656FB0337F8 v3
GUID-56F0C9F7-98F3-4091-B071-53CA5074DC8F v1
497