Settings - ABB Relion 650 Series Technical Manual

Bay control
Hide thumbs Also See for Relion 650 Series:
Table of Contents

Advertisement

Section 10
Monitoring
10.6.5
Table 332:
DRPRDRE Non group settings (basic)
Name
Operation
PreFaultRecT
PostFaultRecT
TimeLimit
PostRetrig
MaxNoStoreRec
ZeroAngleRef
OpModeTest
SetInfoInDRep
416
B12RBDR: INPUT177 to INPUT192 (binary channels 177 to 192)
B13RBDR: INPUT193 to INPUT208 (binary channels 193 to 208)
B14RBDR: INPUT209 to INPUT224 (binary channels 209 to 224)
B15RBDR: INPUT225 to INPUT240 (binary channels 225 to 240)
B16RBDR: INPUT241 to INPUT256 (binary channels 241 to 256)
B17RBDR: INPUT257 to INPUT272 (binary channels 257 to 272)
B18RBDR: INPUT273 to INPUT288 (binary channels 273 to 288)
B19RBDR: INPUT289 to INPUT304 (binary channels 289 to 304)
B20RBDR: INPUT305 to INPUT320 (binary channels 305 to 320)
B21RBDR: INPUT321 to INPUT336 (binary channels 321 to 336)
B22RBDR: INPUT337 to INPUT352 (binary channels 337 to 352)

Settings

Values (Range)
Unit
Off
-
On
0.05 - 9.90
s
0.1 - 10.0
s
0.5 - 10.0
s
Off
-
On
10 - 100
-
1 - 30
Ch
Off
-
On
Disable
-
Enable
A2RADR to A4RADR functions have the same Non group settings (basic) as
A1RADR but with different numbering:
A2RADR: Operation11 to Operation20
A3RADR: Operation21 to Operation30
A4RADR: Operation31 to Operation40
A2RADR to A4RADR functions have the same Non group settings (advanced) as
A1RADR but with different numbering (examples given in brackets):
A2RADR: 11 to 20 (NomValue11, nominal value for analog channel 11)
A3RADR: 21 to 30 (NomValue21, nominal value for analog channel 21)
A4RADR: 31 to 40 (NomValue31, nominal value for analog channel 31)
Step
Default
-
Off
0.01
0.10
0.1
0.5
0.1
1.0
-
Off
1
100
1
1
-
Off
-
Enable
1MRK 511 424-UEN B
Description
Operation Off/On
Pre-fault recording time
Post-fault recording time
Fault recording time limit
Post-fault retrig enabled (On) or not (Off)
Maximum number of stored disturbances
Trip value recorder, phasor reference
channel
Operation mode during test mode
Enable Disturbance report settings
functionality
GUID-E05EEC82-CB90-4E73-B9C9-4C16FD95FCBF v1
Bay control REC650 2.2 IEC
Technical manual
PID-7068-SETTINGS v1

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rec650

Table of Contents