1MRK 511 424-UEN B
10.11.6
Bay control REC650 2.2 IEC
Technical manual
Operation principle
Figure
218
describes the simplified logic of the function.
tWarning
tAlarm
BLOCK
RESET
IN
ADDTIME
tAddToTime
IEC15000322 V1 EN-US
Figure 218:
TEILGAPC Simplified logic
TEILGAPC main functionalities
•
IN: Accumulation of the elapsed time when input IN is high
•
applicable to very long time accumulation (≤99999.9 hours)
•
output ACC_HOUR presents accumulated value in hours and ACC_DAY
presents accumulated value in days
•
accumulated value is retained in a non-volatile memory
•
any retained value is used as initiation value for the integration following
by a restart
•
RESET: Reset of the accumulated value. Consequently all other outputs are
also reset
•
independent of the input IN value
•
reset the value of the nonvolatile memory to zero.
Note that the nonvolatile memory will not reset to zero if the input IN is
high during the reset.
•
reset can be made by activation of input RESET or from LHMI or with
IEC 61850 command
•
ADDTIME: Manually add time to the currently accumulated time
Loop Delay
Transgression Supervision
Time Accumulation
Loop Delay
Section 10
Monitoring
GUID-C7F91D4E-5942-4006-B7C8-4F499E7DC49D v3
OVERFLOW
WARNING
Plus Retain
ACC_HOUR
ACC_DAY
IEC15000322.vsd
ALARM