1MRK 511 424-UEN B
9.3.5
Table 153:
TMAGAPC Group settings (basic)
Name
Values (Range)
Operation
PulseTime
OnDelay
OffDelay
ModeOutput1
ModeOutput2
ModeOutput3
9.3.6
Bay control REC650 2.2 IEC
Technical manual

Settings

Unit
Off
-
On
0.050 - 60.000
s
0.000 - 60.000
s
0.000 - 60.000
s
Steady
-
Pulsed
Steady
-
Pulsed
Steady
-
Pulsed
Operation principle
The trip matrix logic (TMAGAPC) block is provided with 32 input signals and 3
output signals. The function block incorporates internal logic OR gates in order to
provide grouping of connected input signals to the three output signals from the
function block.
Internal built-in OR logic is made in accordance with the following three rules:
1.
when any one of first 16 inputs signals (INPUT1 to INPUT16) has logical
value 1 the first output signal (OUTPUT1) will get logical value 1.
2.
when any one of second 16 inputs signals (INPUT17 to INPUT32) has logical
value 1 the second output signal (OUTPUT2) will get logical value 1.
3.
when any one of all 32 input signals (INPUT1 to INPUT32) has logical value
1 the third output signal (OUTPUT3) will get logical value 1.
By use of the settings ModeOutput1, ModeOutput2, ModeOutput3, PulseTime,
OnDelay and OffDelay the behavior of each output can be customized. The
OnDelay is always active and will delay the input to output transition by the set
time. The ModeOutput for respective output decides whether the output shall be
steady with an drop-off delay as set by OffDelay or if it shall give a pulse with
duration set by PulseTime. Note that for pulsed operation and that the inputs are
connected in an OR-function, a new pulse will only be given on the output if all
related inputs are reset and then one is activated again. For steady operation the
OffDelay will start when all related inputs have reset. Detailed logical diagram is
shown in figure
136
Step
Default
-
Off
0.001
0.150
0.001
0.000
0.001
0.000
-
Steady
-
Steady
-
Steady
Section 9
Description
Operation Off / On
Output pulse time
Output on delay time
Output off delay time
Mode for output ,1 steady or pulsed
Mode for output 2, steady or pulsed
Mode for output 3, steady or pulsed
Logic
PID-6513-SETTINGS v4