ABB Relion 650 Series Technical Manual page 229

Bay control
Hide thumbs Also See for Relion 650 Series:
Table of Contents

Advertisement

1MRK 511 424-UEN B
Bay control REC650 2.2 IEC
Technical manual
Two types of control models can be used. The two control models are "direct with
normal security" and "SBO (Select-Before-Operate) with enhanced security". The
parameter CtlModel defines which one of the two control models is used. The
control model "direct with normal security" does not require a select whereas, the
"SBO with enhanced security" command model requires a select before execution.
The command sequence for a command with control mode SBO with enhanced
security is shown in figure 91, with control mode direct with normal security is
shown in figure 92.
Client
IEC15000416 V2 EN-US
Figure 91:
Example of command sequence for a successful close command
when the control model SBO with enhanced security is used
Reservation
logic
select
SEL_CL = TRUE
RES_RQ = TRUE
RES_GRT = TRUE
SELECTED = TRUE
selectAck/AddCause = 0
requestedPosition = 10
opRcvd = TRUE
opOK = TRUE, tOpOk
operateAck/AddCause = 0
POSITION = 00, timeStamp
POSITION = 10, timeStamp
cmdTermination/AddCause = 0
SELECTED = FALSE
SEL_CL = FALSE
RES_RQ = FALSE
RES_GRT = FALSE
Section 8
Control
SXCBR /
SCSWI
EXE_CL
operateAck/AddCause = 0
POSITION = 00, timeStamp
POSITION = 10, timeStamp
cmdTermination/AddCause = 0
IEC15000416-2-EN.vsdx
SXSWI
223