SYS1
Outline
This changes the operation mode of the high−speed counter based on
the contents specified by the character constant.
Program example
Trigger
R0
10
DF
S
Operands
Relay
Operand
Operand
WX WY WR WL
S
N/A N/A N/A N/A
Explanation of example
When R0 turns on, the operation mode of the high−speed counter CH0 is set to the addition mode.
Description
This changes the operation mode of the high−speed counter specified by No.1 keyword to the operation
mode specified by No.2 keyword.
Keyword setting
High−speed counter setting
HSCn
n: 0 to 9, A, B with FP−X Ry type
n: 0 to 7 with FP−X Tr type
n: 0, 1, 2, 3 with FPΣ
n: 0, 1, 2, 3, 4, 5 with FP0R
UP: Addition input setting
DOWN: Subtraction input setting
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Change high−speed counter
operation mode
Ladder Diagram
Ladder Diagram
SYS1, M
Character constant "M"
Timer/Counter
SV
EV
DT
N/A
N/A
N/A N/A N/A
SYS1, M
HSC1,UP
S
HSC1,UP
No. 1
No. 2
keyword
keyword
Index
Register
register
LD
FL
I
K
N/A
N/A N/A
Basic Instructions
Availability
FPΣ 32k
FP−X Ver 1.10 or more
FP0R
Boolean Non-ladder
Address
Instruction
10
ST
R
11
DF
12
SYS1
M
HSC1,UP
Constant
Index
modifier
modifier
H
M
A
N/A
A:
Available
N/A: Not Available
2 − 129