Basic Instructions
Description
Executes program between the MC and MCE instructions when the execution condition turns on.
When the execution condition is in the off state, the instructions operate as follows.
Instruction
Condition of input and output
OT
All off
KP
Holds the state.
SET
Holds the state.
RST
Holds the state.
TM
Reset
CT
Holds the value.
SR
Holds the value.
Differential
See next page.
Other instructions
Not executed
You must be careful when using one of the instructions below, which are executed by detecting the leading
edge of execution condition such as the differential instruction.
− DF instruction
− Count input for CT instruction
− Count input for F118 (UDC) instruction
− Shift input for SR instruction
− Shift input for F119 (LRSR) instruction
− NSTP instruction
− Differential execution type high−level instruction (this instruction is specified by P and a number)