Basic Instructions
Timer operation when a set value area number is directly specified
When the trigger for a high−level instruction is on, the value is set in the set value area (SV). The
1
following diagram shows an example of using the high−level instruction F0(MV).
X0
F0 MV, K30, SV5
X1
TMX 5, SV 5
T5
When the timer trigger rises from off to on, the setting is transferred from the set value area (SV) to the
2
elapsed value area (EV) with the same number. (The same operation takes place if the mode is
changed to RUN when the trigger is on.)
The value in the elapsed value area (EV) decrements if the trigger stays on every scan.
3
X0
F0 MV, K30, SV5
X1
TMX 5, SV 5
T5
When the value in the elapsed value area (EV) reaches zero, the timer contact (T) with same number
4
turns on.
X1
TMX 5, SV 5
T5
2 − 46
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Set value
SV5
30
Transfers to SV area
1
Y10
Transfers to EV area
2
SV5
30
Decrement
3
Y10
operation
SV5
30
Y10
Decrement operation ends
4
EV5
30
29
28
27
EV5
0