15.3.2 System Errors (From 00F0 1000H)

These are the errors that occur due to any failure within FP7 MC Unit. The system errors are
defined as the fatal errors for the system.
Error
Error name
code
System runaway
System
1000H
If the error occurs, the ALARM
runaway
LED on the unit turns on.
An error occurred in the hardware
Hardware
1001H
test when the power supply
error
turned on.
Any error occurred in the internal
1002H
Unit error
processing.
Any error occurred in the
FROM
execution of writing to FROM.
1010H
write error
(Write error/Verify error/Erase
error)
Tool
Any error occurred in the
operation
communication with a PC when
1020H
abnormal
executing the tool operation on
end
CMI.
Diagnosis
Any error occurred in the
mode
communication with a PC when
1021H
abnormal
executing the diagnosis mode of
end
CMI-Tool.
CPU unit
1030H
ALARM occurred in the CPU unit.
error
(Note 1): To simplify the displays, only the lower four digits (Hex) of each error code are displayed in the above table.
(Note 2): The power supply must be turned off and on again to recover the errors whose "Recovered" column is "-".
Description
Object Recovered
All
axes
All
axes
All
axes
All
axes
All
axes
All
axes
All
axes
15.3 Error Code Table
●: Recoverable, -: Unrecoverable
Countermeasures
-
Turn off the power supply and
turn it on again.
If an error occurs repeatedly,
-
consult your Panasonic
representative.
-
Execute writing to FROM again.
If the error occurred repeatedly,
please contact us.
Check the connection of the
cable connecting the PC and
PLC.
Reboot the PC.
Check the connection of the
cable connecting the PC and
PLC.
Reboot the PC.
Check the condition of the CPU
-
unit. Turn off the power supply
and turn it on again.
15-13