Panasonic AFP7MC16EC User Manual page 59

Fp7 series. motion control unit
Hide thumbs Also See for AFP7MC16EC:
Table of Contents

Advertisement

5. Select "Scan EtherCAT Network" from the context menu.
FP7 MC Unit executes scanning the network. The information on Servo Amplifiers
A6B/A5B connected to FP7 MC Unit is displayed in the project explorer in the
connection order.
KEY POINTS
It takes approximately 10 seconds for one axis to complete the scanning of
EtherCAT network.
"Scan EtherCAT network" can be executed when the "EC L/A" LED on FP7
MC Unit is lit or blinking. Possible situations are as follows.
 Unit state and network scanning operation
LEDs of FP7 MC Unit
EC L/A
EC RUN
ON
OFF
Flickering
ON
ON or
ON
Flickering
Possible case and confirmation method
ERR
"Network configurations verify error" occurs. In this case,
even when the ERR LED is lit, the network scanning can
be executed.
ON
This error also occurs when using FP7 MC Unit for the
first time as the information on the network configuration
is not downloaded to FP7 MC Unit.
"Network configurations verify error" may occur as the
rotary switches on Servo Amplifier A6B/A5B are not set to
ON
"00". Set the rotary switches to "00" and restart the power
supply.
The situation that the network configuration information
has been downloaded and the number of connected
OFF
servo amplifiers matches is possible. The network
scanning can be executed.
4.4 Setting of Network Configuration
Network
scanning
Executable
Not
executable
Executable
4-13