Automatic Operation (Synchronous Control)
The cam pattern reading results are as follows.
Unit
Axis
memory
Name
no.
no. (Hex)
Cam
pattern
-
UM 66F98
reading
result
9-46
Default Unit
Setting range and description
- The result of reading processing (response code) is stored.
Code
H0
HFF01
H0
-
HFF10
HFF11
Name
Description
Normal end
-
Cam pattern
The cam
number
pattern
setting error
setting value
is out of the
settable
range.
Cam pattern
An axis in
reading not
synchronous
executable
operation
error 1
exists.
Cam pattern
An operating
reading not
axis exists.
executable
error 2
Countermeasures
-
Check the set value
of the cam pattern
number.
Cancel the
synchronous
operation and
execute the reading.
Execute the reading
when no operating
axis exists.