15.3 List of System Codes

15.3.1 System Errors (From 1000H)

These are the errors that occur due to any failure within the positioning unit. The system errors are
defined as the fatal errors for the system. Except for some items, the power supply must be turned off
and on again to recover from the errors.
Error
Error name
code
System
1000H
runaway
Hardware
1001H
error
1002H Unit error
System
1003H
processing
error
FROM writing
1010H
error
Tool
1020H
operation
abnormal end
High-order
1030H
CPU error
Description
System runaway (If the error occurred,
the ALARM LED on the positioning
unit is lighted.
An error occurred in the hardware test
when the power supply turned on.
Any error occurred in the internal
processing.
An error occurred in the system
processing due to any reason.
An error occurred when the positioning
settings were written in the positioning
unit.
Item: Writing error
Verify error
Erase error
An error occurred in the
communication with a PC in the tool
operation by the Configurator PM.
An alarm occurred on a higher-order
CPU (control unit or CPU).
A: Available N/A: Not available
Object
Clear
All axes
N/A
Turn off the power supply and
turn it on again.
All axes
N/A
If the error occurred repeatedly,
please contact us.
All axes
N/A
Check the settings.
If the setting values are correct
All axes
A
and the error occurred repeatedly,
please contact us.
Rewrite into the FROM again.
All axes
A
If the error occurred repeatedly,
please contact us.
Check the connection of the
RS232C cable connecting the PC
All axes
A
and PLC.
Reboot the PC.
Check the status of higher-order
All axes
N/A
CPU.
Turn on the power supply again.
Countermeasures
15-5

Advertisement

Table of Contents

Troubleshooting

loading

Table of Contents