VACON® 100 FLOW
Application Guide
10.2.8 (ID 6) Motor Voltage
Location in the menu with default settings: V2.1.9 (In Multimonitor menu)
Location in the menu: V2.3.9 (In Basic menu)
This monitoring value shows the actual output voltage to the motor.
10.2.9 (ID 7) DC Link Voltage
Location in the menu with default settings: V2.1.7 (In Multimonitor menu)
Location in the menu: V2.3.10 (In Basic menu)
This monitoring value shows the measured voltage in the DC link of the drive.
10.2.10 (ID 8) Unit Temperature
Location in the menu with default settings: V2.1.6 (In Multimonitor menu)
Location in the menu: V2.3.11 (In Basic menu)
This monitoring value shows the measured heat sink temperature of the drive.
The unit of measurement is degrees Celsius or Fahrenheit, depending on parameter C/F Selection (ID 1197) value.
10.2.11 (ID 9) Motor Temperature
Location in the menu: V2.3.12
This monitoring value shows the calculated motor temperature in percentage of the nominal working temperature.
When the value rises above 105%, motor thermal protection fault occurs.
10.2.12 (ID 1228) Motor Preheat
Location in the menu: V2.3.13
This monitoring value shows the status of the motor preheat function.
10.2.13 (ID 1054) kWh Trip Counter Low
Location in the menu: V2.3.15
This monitoring value shows the actual value of the kWh counter (energy counter). When the value of the counter goes higher than
65535, the counter is restarted from 0.
10.2.14 (ID 1067) kWh Trip Counter High
Location in the menu: V2.3.16
This monitoring value shows how many times the kWh counter (energy counter) has spun around.

10.3 I/O

10.3.1 (ID 15) SlotA DIN 1,2,3
Location in the menu: V2.4.1
This monitoring value shows the status of the digital inputs 1–3 in slot A (standard I/O).
10.3.2 (ID 16) SlotA DIN 4,5,6
Location in the menu: V2.4.2
This monitoring value shows the status of the digital inputs 4–6 in slot A (standard I/O).
10.3.3 (ID 17) SlotB RO 1,2,3
Location in the menu: V2.4.3
This monitoring value shows the status of the relay outputs 1–3 in slot B.
10.3.4 (ID 59) Analog Input 1
Location in the menu: V2.4.4
This monitoring value shows the value of the analog input signal as a percentage of the used range.
Danfoss A/S © 2023.08
Monitoring Value Descriptions
AB298035655957en-000201 / DPD01083 | 153