11.11.1.3 (ID 727) Undervoltage Fault
Location in the menu: P3.9.1.4
Use this parameter to select if undervoltage faults are saved to the fault history or not.
11.11.1.4 (ID 702) Response to Output Phase Fault
Location in the menu: P3.9.1.5
Use this parameter to select the response of the drive to an 'Output Phase' fault. If the measurement of the motor current detects
that there is no current in 1 motor phase, an output phase fault occurs. See P3.9.1.2.
11.11.1.5 (ID 733) Response to Fieldbus Communication Fault
Location in the menu: P3.9.1.6
Use this parameter to select the response of the drive to a fieldbus communication fault. If the data connection between the master
and the fieldbus board is defective, a fieldbus fault occurs.
11.11.1.6 (ID 734) Slot Communication Fault
Location in the menu: P3.9.1.7
Use this parameter to select the response of the drive to a 'Slot Communication' fault. If the drive detects a defective option board, a
slot communication fault occurs. See P3.9.1.2.
11.11.1.7 (ID 732) Thermistor Fault
Location in the menu: P3.9.1.8
Use this parameter to select the response of the drive to a 'Thermistor' fault. If the thermistor detects too high temperature, a ther-
mistor fault occurs. See P3.9.1.2.
11.11.1.8 (ID 748) PID Soft Fill Fault
Location in the menu: P3.9.1.9
Use this parameter to select the response of the drive to a 'PID Soft Fill' fault. If the PIDFeedback value does not reach the set level
within the time limit, a soft fill fault occurs. See P3.9.1.2.
11.11.1.9 (ID 749) Response to PID Supervision Fault
Location in the menu: P3.9.1.10
Use this parameter to select the response of the drive to a 'PID Supervision' fault. If the PID feedback value is not within the supervi-
sion limits for longer than the supervision delay, a PID supervision fault occurs. See P3.9.1.2.
11.11.1.10 (ID 757) Response to External PID Supervision Fault
Location in the menu: P3.9.1.11
Use this parameter to select the response of the drive to a 'PID Supervision' fault. If the PID feedback value is not within the supervi-
sion limits for longer than the supervision delay, a PID supervision fault occurs. See P3.9.1.2.
11.11.1.11 (ID 703) Earth Fault
Location in the menu: P3.9.1.12
Use this parameter to select the response of the drive to an 'Earth Fault'.
If the measurement of the current detects that the sum of the motor phase currents is not 0, an earth fault occurs. See P3.9.1.2.
N O T I C E
It is possible configure this fault only in enclosure sizes MR7, MR8, MR9, MR10, MR11, and MR12, and also MR6 600 V & 690 V.
11.11.1.12 (ID 183) Preset Alarm Frequency
Location in the menu: P3.9.1.13
Use this parameter to set the frequency of the drive when a fault is active and the response to the fault is set to 'Alarm + Preset
Frequency'.