12.3.7 Fault Code 5, ID 40 - Charging Switch
Cause
The charging switch is closed and the feedback information is OPEN.
•
operation malfunction
•
defective component
Troubleshooting
•
Reset the fault and restart the drive.
•
Check the feedback signal and the cable connection between the control board and the power board.
•
If the fault occurs again, ask for instructions from your nearest distributor.
12.3.8 Fault Code 7, ID 60 - Saturation
Cause
•
Defective IGBT.
•
De-saturation short circuit in the IGBT.
•
A short circuit or an overload in the brake resistor.
Troubleshooting
•
This fault cannot be reset from the control panel.
•
Switch off the power.
•
DO NOT RESTART THE DRIVE or CONNECT THE POWER!
•
Ask for instructions from the factory.
12.3.9 Fault Code 8, ID 600 - System Fault
Cause
•
There is no communication between the control board and the power unit.
Troubleshooting
•
Reset the fault and restart the drive.
•
Download the latest software from the Danfoss Drives website. Update the drive with it.
•
If the fault occurs again, ask for instructions from your nearest distributor.
12.3.10 Fault Code 8, ID 601 - System Fault
Cause
•
There is no communication between the control board and the power.
Troubleshooting
•
Reset the fault and restart the drive.
•
Download the latest software from the Danfoss Drives website. Update the drive with it.
•
If the fault occurs again, ask for instructions from your nearest distributor.
12.3.11 Fault Code 8, ID 602 - System Fault
Cause
•
Defective component.
•
Operation malfunction.
Troubleshooting
•
Reset the fault and restart the drive.
•
Download the latest software from the Danfoss Drives website. Update the drive with it.
•
If the fault occurs again, ask for instructions from your nearest distributor.