Danfoss VACON 100 FLOW Series Application Manual page 30

Hide thumbs Also See for VACON 100 FLOW Series:
Table of Contents

Advertisement

VACON® 100 FLOW
Application Guide
Reference-
potentiome-
ter
1...10 kΩ
mA
RUN
FAULT
Illustration 6: The Default Control Connections of the Standard and HVAC Applications
*) Available only in VACON
100 X. **) For the DIP switch configurations in VACON
®
ual.
30 | Danfoss A/S © 2023.08
Terminal
1
+10 Vref
AI1+
2
AI1-
3
AI2+
4
AI2-
5
6
24Vout
7
GND
DI1
8
DI2
9
DI3
10
CM
11
24 V out
12
GND
13
14
DI4
15
DI5
16
DI6
17
CM
18
AO1+
19
AO1-
30
+24 Vin
A
RS485
B
RS485
21
R O1/1 NC
22
R O1/2 CM
23
R O1/3 NO
24
R O2/1 NC
25
R O2/2 CM
26
R O2/3 NO
28
TI1+
29
TI1-
32
R O3/2 CM
33
R O3/3 NO
Standard I/O board
Signal
Reference output
Analog input 1 +
Analog input 1 -
Analog input 2 +
Analog input 2 -
24 V auxiliary voltage
I/O ground
Digital input 1
Digital input 2
Digital input 3
Common for DI1-DI6
24 V auxiliary voltage
I/O ground
Digital input 4
Digital input 5
Digital input 6
Common for DI1-DI6
Analog output 1 +
Analog output 1 -
24V auxiliary
input voltage
Serial bus, negative
Serial bus, positive
Relay output 1
Relay output 2
Thermistor input
Relay output 3
100 X, see the VACON
®
Description
Frequency reference
(default 0...10 V)
Frequency reference
(Default 4...20 mA)
Start forward
Start reverse
External fault
DI4
DI5
Freq. ref.
Open
Open
Analog input 1
Closed
Open
Preset Freq. 1
Open
Closed
Preset Freq. 2
Closed
Closed
Preset Freq. 3
Fault reset
Output
frequency
0...20 mA)
Modbus RTU,
N2, BACnet
RUN
FAULT
*)
**)
READY
100 X Installation man-
®
AB298035655957en-000201 / DPD01083
Applications