VACON® 100 FLOW
Application Guide
Table 9: M1 Quick Setup
Index
Parameter
1.2
Application
1.3
Minimum Frequency
Reference
1.4
Maximum Frequency
Reference
1.5
Acceleration Time 1
1.6
Deceleration Time 1
1.7
Motor Current Limit
1.8
Motor Type
1.9
Motor Nominal Volt-
age
1.10
Motor Nominal Fre-
quency
1.11
Motor Nominal Speed
1.12
Motor Nominal Cur-
rent
1.13
Motor Cos Phi (Power
Factor)
1.14
Energy Optimization
1.15
Identification
1.16
Start Function
1.17
Stop Function
1.18
Automatic Reset
64 | Danfoss A/S © 2023.08
Min
Max
Unit
Default
0
4
2
0.00
P1.4
Hz
0.0
P1.3
320.0
Hz
50.0/60.0
0.1
3000.0
s
5.0
0.1
3000.0
s
5.0
IH*0.1
I
A
Varies
S
0
2
0
Varies
Varies
V
Varies
8.0
320.0
Hz
50/60
24
19200
RPM
Varies
IH * 0.1
I
A
Varies
S
0.30
1.00
Varies
0
1
0
0
2
0
0
1
0
0
1
0
0
1
0
ID
Description
212
0 = Standard
1 = HVAC
2 = PID Control
3 = Multi-pump (single drive)
4 = Multi-pump (multidrive)
101
102
103
104
107
650
0 = Induction Motor
1 = Permanent Magnet Motor
2 = Reluctance Motor
110
Find this value U
on the nameplate of the mo-
n
tor.
NOTE! Find out if the motor connection is Delta
or Star.
111
Find this value f
on the nameplate of the mo-
n
tor.
112
Find this value n
on the nameplate of the mo-
n
tor.
113
Find this value I
on the nameplate of the mo-
n
tor.
120
Find this value on the nameplate of the motor.
666
0 = Disabled
1 = Enabled
631
0 = No action
1 = At standstill
2 = With rotation
505
0 = Ramping
1 = Flying Start
506
0 = Coasting
1 = Ramping
731
0 = Disabled
1 = Enabled
AB298035655957en-000201 / DPD01083