VACON® 100 FLOW
Application Guide
Troubleshooting
•
Check the loading.
•
Check the motor.
•
Check the cables and connections.
•
Make an identification run.
•
Set the acceleration time longer (P3.4.1.2 and P3.4.2.2).
12.3.3 Fault Code 2, ID 10 - Overvoltage (Hardware Fault)
Cause
The DC link voltage is higher than the limits.
•
too short a deceleration time
•
high overvoltage spikes in the supply
Troubleshooting
•
Set the deceleration time longer (P3.4.1.3 and P3.4.2.3).
•
Activate the overvoltage controller.
•
Check the input voltage.
12.3.4 Fault Code 2, ID 11 - Overvoltage (Software Fault)
Cause
The DC link voltage is higher than the limits.
•
too short a deceleration time
•
high overvoltage spikes in the supply
Troubleshooting
•
Set the deceleration time longer (P3.4.1.3 and P3.4.2.3).
•
Activate the overvoltage controller.
•
Check the input voltage.
12.3.5 Fault Code 3, ID 20 - Earth Fault (Hardware Fault)
Cause
The measurement of current tells that the sum of the motor phase current is not zero.
•
an insulation malfunction in the cables or the motor
•
a filter (dU/dt, sine) malfunction
Troubleshooting
•
Check the motor cables and the motor.
•
Check the filters.
12.3.6 Fault Code 3, ID 21 - Earth fault (Software Fault)
Cause
The measurement of current tells that the sum of the motor phase current is not zero.
•
an insulation malfunction in the cables or the motor
•
a filter (dU/dt, sine) malfunction
Troubleshooting
•
Check the motor cables and the motor.
•
Check the filters.